Flow Line Options Corp. (Flo-Corp)
9009 S. Freeway Drive #4
Macedonia, OH 44056
Toll Free: 1-877-FLO-LINE
             (1-877-356-5463)
Phone:    330-468-0180
Fax:        330-468-0185

Print friendly
version of page
Subscribe to RSS feed


DeltaSpan External Pressure Transmitter

Unique Features


  • Corrosion resistant 316 SS transducer with cable or junction box termination
  • Small, rugged transducer is ideal for fluid handling equipment

DeltaSpan LD30

DeltaSpan External Pressure Transmitter

The general purpose two-wire pressure transmitter is offered in two termination packages and provides contact level measurement up to 69' or 21.1m of water column. Select the -S_01 for cable termination or the -S_11 for conduit termination with an integral junction box. The transmitter is best applied with clean liquid or gas media including water, oil and air. Application examples include irrigation equipment, pumping systems and compressors.


Service: Compatible gases or liquids.
Wetted Materials: Body: 316 SS, 316L SS
Accuracy: +/-0.25% of full scale.
Temperature Limit: 0 to 200°F (-18 to 93°C).
Compensated Temperature Range: 0 to 175°F (-18 to 79°C).
Thermal Effect: Less than +/-0.02%/°F.
Pressure Limit: -S0_1: 10 psig (maximum) / 50 psig (over pressure)
-S2_1: 30 psig (maximum) / 150 psig (over pressure)
-S4_1: 60 psig (maximum) / 300 psig (over pressure)
Power Requirement: 13 to 30 VDC.
Output Signal: 4 to 20 mA, 2-wire.
Response Time: 50 ms.
Max. Loop Resistance: 1300 Ohms @ 30 VDC
Current consumption: 38 mA (maximum)



Electrical Connections: -S_01: Cable (9' length)
-S_11: Conduit Housing with Terminal Block
Process connection: ?" male NPT
Enclosure rating: NEMA 4X (IP 66)
Mounting Orientation: Mount in any position.
Weight: 10 oz. (283 g).
Agency approval (CE): EN 55022
EN 55024
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6


DeltaSpan LD30

DeltaSpan External Pressure Transmitter


  • This transmitter is best applied with clean liquid or gas media including water, oil and air.
  • Application examples include irrigation equipment, pumping systems and compressors.

DeltaSpan LD30

Accessories


For integral conduit termination and process mount, order the LD90-1001 (2" NPT) or LD90-1061 (1 1/2 G) installation kit. Each kit includes a PP junction box rated NEMA 4X, PP plug fitting and nylon cable connector.


 

LD90-1001 Application Photo