EchoSwitch II, Second Generation Non-Contact Level Switch and Controller
Unique Features
- Simple digital push button configuration, no more target calibration.
- Pump simplex, duplex and triplex option.
- Integrated timer for pump/valve delay and pump alternation.
- Available in a 7.5m (24.6') or 2.5m (8.2') maximum range.
- 10 cm (4") miniature dead band optimizes the filling capacity of sumps or vessels.
Description
The general purpose ultrasonic switch and controller provides non-contact level detection up to 24.6' (7.5 m) with 3 SPDT 60 VA 1A relays. EchoSwitch II features digital push button configuration, eliminating target calibration. Each relay can be configured on a single set point to control pumps, valves or alarms. In addition, all 3 relays can be simplexed, duplexed or triplexed. EchoSwitch II now features an integrated timer with pump/valve delay and timed pump alternation. The switch is well suited for a broad range of corrosive, waste and slurry type media. EchoSwitch II is broadly selected for atmospheric day tanks, pump lift stations and waste sump applications.
| Range: | LU77: 4 to 8.2' (10 cm to 2.5m) LU78: 8 to 24.6' (20 cm to 7.5m) |
| Repeatability: | 0.25 (6.35 mm) |
| Effective Beam width: | 3 (7.6 cm) dia. |
| Dead band: | LU77: 4” (10 cm) LU78: 8” (20 cm) |
| LCD indication: | Level and relay status |
| Configuration: | Push button |
| Supply voltage: | 95-250 VAC |
| Contact type: | (3) SPDT relays |
| Contact rating: | 60 VA, 1A max |
| Contact fail-safety: | Programmable / selectable |
| Temp. comp.: | Automatic |
| Electronics temp.: | F: -7° to 140° C: -20° to 60° |
| Pressure: | MWP = 30 PSI |
| Enclosure rating: | NEMA 4X (IP65) |
| Enclosure vent: | Water tight membrane |
| Encl. material: | Polycarbonate, UV |
| Encl: hardware: | Brass and stainless |
| Trans. material: | PVDF |
| Process mount: | LU77: 1” NPT (1” G) LU78: 2” NPT (2” G) |
| Mount. gasket: | Viton® |
| Conduit entrance: | Dual, 1/2” NPT |
| Classification: | General purpose |
| Compliance: | RoHS |
| Approvals: | CE |
Typical Applications
- The EchoSwitch II is well suited for a broad range of corrosive, waste and slurry type media.
- EchoSwitch II is broadly selected for atmospheric day tank, pump lift station and sump applications.
- Designed for day tank, process vessel and waste sump applications.

Accessories
LM50 Side Mount Bracket - Wall Mount
Mount any 2" NPT transducer - Allows 3" clearance from wall - Perfect for Flow Line Options' 3 inch beam angle. LM50-5001-01 bracket for EchoPod 1" NPT